Main Building Barrier Box Secondary Building
Center screw — Connect to
main building protective
ground (or ground terminal of
Barrier Box Rack Mounting
Kit). Use 18AWG (minimum)
wire with a green and yellow
sleeve.
Right-hand screw
Connect to ground point on
Phone module using ground
cable supplied with barrier
box.
Center screw — Connect
to main building protective
ground. Use 18AWG
(minimum) wire with a green
and yellow sleeve.
Right-hand screw — Not
used.
The following wires must be kept apart, that is, the wires cannot be routed in the same bundle:
• Earth leads from the barrier box to the phone modules.
• Internal wires, for example extension leads going directly to the phone modules.
• Wires from external telephone going directly to the barrier boxes.
Rack mounting barrier boxes
About this task
Where more than 3 phone barrier boxes are used they must be rack mounted. The Barrier Box
Rack Mounting Kit (SAP Code 700293905) supports up to 8 phone barrier boxes.
Procedure
1. Unscrew the two screws arranged diagonally at the front of each barrier box and
use these same screws to reattach the barrier box to the rack mounting strip.
2. Each barrier box is supplied with a solid green ground wire connected to its
functional ground screw. Remove and discard this wire.
3. Connect a green/yellow ground wire to the protective earth screw in the center of
the point on the back of the barrier box.
4. The rack mounting strip has threaded M4 earthing pillars. Connect the other end of
the barrier box ground wire, using M4 washers and nuts, to the earthing pillar on
that side of the rack mounting strip.